| TYPICAL PANEL / PUMP PROBLEMS | |
| PROBLEM | SOURCE OF PROBLEM |
| 1) PANEL OVERLOAD TRIPS | Low or incorrect voltage Heaters not properly adjusted Impeller blocked or bound Impeller rotating in wrong direction ( 3 phase) Motor overheating Undersized wire in branch circuit Missing leg in 3 phase power circuit |
| 2) PUMP SHORT CYCLING | Float switches out of adjustment Check valve not closing when pump stops Undersized basin or pump Pump overload problem Motor winding problem |
| 3) START CAPACITOR BLOWS (Single phase ) |
Improper connections in starting circuit Defective or malfunctioning start relay Voltage to low Capacitors undersized Undersized wire in branch circuit Not enough head in the system Short-cycling pump Distance between pump & panel is to far |
| 4) PUMP RUNS IN MANUAL MODE ONLY | Defective float switch #1 or #2 Float switch #1 out of adjustment Defective alternator board or relay Loose wire causes an open circuit Junction box float switch connections incorrect |
| 5) PUMP WILL NOT OPERATE IN MANUAL OR AUTOMATIC MODE | No control power Defective transformer Open fuse or circuit breaker Overload heater tripped and not re-set Bad motor contactor Malfunctioning start capacitor ( single phase) Pump not connected properly Wrong voltage Defective pump cable or motor Junction box pump connections incorrect |
| 6) BLOWN FUSE OR OPEN CIRCUIT BREAKER | Short to ground in panel Defective relay or shorted contactor coil Moisture in panel Bad wire in branch circuit Grounded power cord Moisture has entered the pump housing Grounded motor |
| 7) ONLY ONE PUMP CYCLES IN A DUPLEX SYSTEM | Defective switch or relay in alternator circuit Defective motor contactor Overload , fuse, or breaker open Inoperable lag (#3) float switch Pump selector switch in off position Defective pump motor |
| 8) ALARM ACTIVATES ON A REGULAR BASIS | Alarm float out of adjustment Undersized pumps Impeller turning in wrong direction (3 phase) Mal-functioning pump in a 3-float duplex system System is air-locking |
| 9) INCONSISTENT PUMP OPERATION | Impeller is getting bound System is air-locking Impeller rotating in wrong direction (3 ph) Malfunctioning starting circuit (single phase) Defective motor starter Motor windings deteriorating |