![]() |
![]() |
| PUMP SYSTEM TROUBLE SHOOTING | |
| When trouble shooting a pump system, you will find the following information, supplies, and equipment to be helpful in the field. | |
| # 1) | AN ACCURATE PANEL WIRING DIAGRAM |
| # 2) | A SET OF JUMPER WIRES |
| # 3) | VOLTAGE , OHM AND AMP METER |
| # 4) | START-UP REPORT |
| # 5) | SPARE PANEL CONTROL FUSES |
| # 6) | EXTRA CAPACITORS/RELAYS FOR SINGLE PHASE SYSTEM |
| # 7) | MOTOR WINDING RESISTANCE VALUES |
| # 8) | PUMP PERFORMANCE & ELEC. DATA |
| # 9) | TROUBLE SHOOTING CHECK LIST |
| Whenever working around electrical equipment, think safety. The wrong move can have dangerous consequences. Use the panel disconnects to remove system power . Use your voltage meter to verify that the systems power is deactivated. | |
| Objective...Determine where the problem exists | |
| # 1) | WITH THE PUMPS |
| # 2) | IN THE PANEL |
| # 3) | WITH THE FLOAT SWITCHES |
| The following steps will assist in your efforts to isolate the problem area: | |
| STEP # 1) | Make a visual overview of the
system FAMILIARIZE YOURSELF WITH THE SYSTEM COMPONENTS VERIFY THE PUMP VOLTAGE TO THE SYSTEM POWER SOURCE PUMP CAPABILITY VS. SYSTEM CHARACTERISTICS VERIFY THAT ALL ELECTRICAL CONNECTIONS TO PANEL ARE CORRECT INSPECT SYSTEM FOR ABUSE OR DAMAGE INSPECT EVERY INCH OF CORDAGE FOR DAMAGE REVIEW START-UP REPORTS INSTALLATION CHECK LIST |
| STEP # 2) | Check the supply voltage at the panel. |
| STEP #3) | Check the control voltage (usually 120 volt) |
| STEP #4) | Check the alarm circuit with test switch, jumper, or float |
| STEP #5) | Operate each pump by placing
selector switch in hand mode CHECK THE PUMP RUN LIGHT TAKE AN AMP AND VOLTAGE READING WITH PUMP RUNNING CHECK FOR PROPER ROTATION (3 PHASE SYSTEM) |
| STEP #6) | Simulate float switch operation
with jumper wires
repeat through numerous lead/lag cycles TAKE A VOLTAGE READING WITH BOTH PUMPS OPERATING |
| STEP #7) | Check motor windings...must
disconnect from panel CHECK RESISTANCE THROUGH EACH WINDING CHECK EACH MOTOR LEAD TO GROUND...THERE SHOULD BE NO CONTINUITY CHECK INSULATION WITH MEGOHMMETER, SHOULD BE GREATER THAN 10 |
| During the above steps, stop and investigate if you detect a malfunction...if all components operate correctly during the above steps you will want to check out your float switches and all junction box connections (if you are using one). | |
| Web pages created and maintained by Zoeller Company © 2008 Zoeller Company. All rights reserved. Send information regarding this web site to webmaster@zoeller.com |